Fault | Fault symptoms&possible causes | Troubleshooting solutions |
AC Over-voltage |
AC input voltage is too high | 1. If the voltage exceeds 264Vac for a short time, wait for the grid to return to the normal voltage range by itself. |
2. Check the background monitoring data and analyze it. If the voltage in this area is over-voltage for a long time, you can increase the input over-voltage protection point through the configuration software, up to 300Vac. | ||
3. If the fault cannot be eliminated, please contact us. | ||
AC Under-voltage |
AC input voltage is too low | 1. If the voltage is lower than 140Vac for a short time, wait for the grid to return to the normal voltage range by itself. |
2. Check the background monitoring data and analyze it. If the voltage in this area is under-voltage for a long time, you can increase the input under-voltage protection point through the configuration software. The minimum can be 140Vac. | ||
3.If the fault cannot be eliminated, please contact us. | ||
AC Over-current |
AC input current is too large | 1. Disconnect the leakage/over-current protection circuit breaker of the distribution box immediately |
2. Check whether there is low impedance or short circuit between the two wires of the AC EV Charger output line. | ||
3. If the fault cannot be eliminated, please contact us. | ||
AC Over frequency |
AC input frequency is too high | 1. If the frequency exceeds 55HZ for a short time, wait for the network to return to the normal frequency range by itself. |
2. Check the input voltage frequency in the background monitoring data. If it is too high for a long time, please contact the power supply department for processing. | ||
AC Under frequency |
AC input frequency is too low | 1. If the frequency is lower than 45HZ for a short time, wait for the waiting network to return to the normal voltage range by itself. |
2. Check the background monitoring data and analyze it. If the frequency in this area is over-frequency for a long time, you can increase the input over-frequency protection point through the configuration software, which can be as low as 40Hz. | ||
3. If the fault cannot be eliminated, please contact us. | ||
Over-temperature |
Over-temperature of inside of AC Charging Station | 1. Check the installation environment of the AC pile, check whether there are other heating devices nearby, and ensure that the ambient temperature is below 60°. |
2. If the fault cannot be eliminated, please contact us. | ||
Leakage current |
The earth leakage current is too high | 1. Disconnect the leakage/over-current protection switch of the distribution box immediately. |
2. Check whether the output wire of the AC pile is damaged or has low impedance or short circuit to the ground | ||
3. If the fault cannot be eliminated, please contact us. | ||
Earth fault | The input/output improperly grounded or the input L/N is inversely connected | 1. Disconnect the leakage/over-current protection switch of the distribution box immediately. |
2. Check whether the input/output wire of the AC charging station is properly grounded, and whether the input L/N is connected in the normal order. | ||
3. If the fault cannot be eliminated, please contact us. | ||
Abnormal communication (networking mode) | The communication is not good of background of AC Charging Station | 1. Check whether the connection of the network cable is correct and reliable. |
2. Check whether the EV charging station configuration is correct in the background. | ||
3. If the fault cannot be eliminated, please contact us. | ||
Charging gun improperly connected | The abnormal connection of charging gun | 1. Check whether the connection of the EV charging cable is correct and reliable. |
2. If the fault cannot be eliminated, please contact us. |